Prysmian’s Low Voltage AIRGUARD Control Cables are primarily designed for applications in the harsh environments found in the heavy industrial and offshore markets. Its rugged polymeric AIRBAG armor and chemical barrier protection package makes it the ideal cable choice for tough installation and environmental conditions. AIRGUARD provides the solution to the deficiencies often encountered with MC-HL cables including armor breakage encountered during installation and in applications requiring recurring bending after installation, as well as poor performance in areas of high vibration (e.g. motor connections). It also provides a safer and lower installed cost alternative to MC-HL cables due to faster, “No Knife/ No Saw” cable preparation, and substantially reduced cost of cable glands.
Conductor: Class B stranded bare, soft drawn copper circuit conductors
Insulation: 90oC Heat and moisture resistant cross-linked polyethylene (XLPE) meeting the requirements of UL-44 for Type XHHW-2 conductors for wet or dry locations
Fillers: Extruded filler belt
Polymeric Armor/Environmental Barrier: Foamed polymeric AIRBAG™ layer affords superior mechanical and environmental protection of the cable core
Outer Sheath: Heat, moisture, hydrocarbon, and sunlight resistant thermoplastic
Specifications
• ASTM B3 & ASTM B8 Class B Soft Drawn Concentric Lay Stranded Bare Copper Conductors
• ICEA S-82-532 (NEMA WC57) Control Cable Rating
• UL 44 (XHHW-2) 600V XHHW-2 Multiple Conductors Direct Buried Sunlight Resistant Oil Resistant
• UL 1202/FT-4 Flame Retardant
• UL 1277 NEC Article 336.10(7) TC-ER Exposed Run Rating NEC
• UL 2225 TC-ER-HLArticle 501.10(A)(2)(3) Class I Division 1 Hazardous Locations
• NEC Article 505.15(B)(1)(i) TC-ER-HL Class I Zone 1 Hazardous Locations
• CSA 22.2 No. 03-40oC/-35oC Cold Bend/ Cold Impact
• MSHA Mine Safety & Health Administration
Technical Specification | |
Number and Circuit Conductor Size |
7/C #10 AWG |
Insulation Thickness Mils |
30 |
Conductor Diameter Inches |
00.113 |
Nominal Overall Insulation (OD) Inches |
0.177 |
Nominal Overall Cable (OD ) Inches |
00.915 |
Nominal Cable Weight lbs/Mft | 564 |
Minimum Bending Radius Inches |
3.7 |
Ampacity (Amps) ‡90°c | 28 |
Gland, Explosion Proof, Class 1 Division 1, Barrier Type | 424BT04 |
Prysmian and Draka Cable Part Number | 394074 |