Conductor: Soft annealed stranded tinned copper
per ASTM B 33. A polyester tape separator is used over
the conductor.
Insulation: Bostrig Type P chemically cross-linked
polyolefin (XLPO), meeting IEEE 1580.
Jacket: Flame-Retardant Thermosetting CPE (Chlorinated
Polyethylene) applied over the armor in accordance with
the requirements of IEEE-1580-2010. Thickness as shown in
tables on opposite page. Arctic Neoprene (Type N) also
available as an option.
Armor: Braided bronze in accordance with IEEE 1580.
Sheath: Flame-Retardant Thermosetting CPE (Chlorinated
Polyethylene) applied over the armor in accordance with
the requirements of IEEE-1580-2010. Thickness as shown
in tables on opposite page. Arctic Neoprene (Type N) also
available as an option.
Applications
Bostrig™ Type P Marine and Offshore Cable is primarily
designed for power, control, signal, and instrumentation
applications for marine vessels, and offshore production
facilities.
Bostrig™ cables have excellent resistance to oil, abrasion,
moisture, vibration, sunlight, and ester based mud
(Type P- MR). They are suitable for use in Class 1,
Division 1 offshore applications (armored & sheathed).
The standard insulation has a continuous operating
temperature of 125°C, allowing for higher ampacity levels.
These cables also meet cold bend requirements of -40°C
and cold impact of -35°C (CSA 22.2 N0. 0.3).
This product may be manufactured in an unarmored or
armored and sheathed version.
Features/Ratings
• Superior resistance to oil, abrasion, moisture,
sunlight, mud, crush and impact
• High strand count conductors provide superior
flexibility
• Higher allowable conductor operating temperature
results in increased ampacity
• Cold bend/ cold impact of -40°/ -35°C in accordance
with CSA 22.2 No. 0.3
• Flame retardant in accordance with IEEE 1202 and
IEC 60332-3-22 Category A
• Meets IEEE standards for 600V and performance
requirements of IEC standards for 0.6/1 kV
• Armored and sheathed cables suitable for use in
Class 1 Division 1 and Zone 1 hazardous locations
offshore
Approvals
• IEEE 1580 and IEEE 45- Marine Shipboard Cable
• UL 1309- Marine Shipboard Cable Type X110
• CSA 22.2 No. 245- Marine Shipboard Cable Type X110
• Det Norske Veritas (DNV)
• American Bureau of Shipping (ABS)
• Transport Canada Approved AMS400-20-2
• Transport Canada 8700-20-2
• Lloyd’s Register of Shipping
• United States Coast Guard-46CFR
Technical Specification | |
Conductor Size | 18 AWG |
Number of Conductor |
4 |
Type Designation |
C18PNBS-4 |
Insulation Thickness (in) | 0.030 |
Insulation Thickness (mm) | 0.76 |
Sheath Thickness(in) |
0.060 |
Sheath Thickness (mm) | 1.5 |
Cable Diameter(in) |
0.570 |
Cable Diameter (mm) | 14.5 |
Cable Weight (Lbs/mft) |
225 |
Cable Weight (kg/km) | 335 |
Prysmian and Draka Part Number | T26251 |