Technical Specifications: | |
Phase Conductor Size AWG: | 1/0 |
Phase Conductor Stranding: | 19/w |
Phase Conductor Insulation Thickness: | 60 mls |
Base Neutral Messenger Size AWG: | 1/0 |
Base Neutral Strand: | 7/w |
Bare Neutral Messenger Breaking Strength: | 1990 Lbs |
Weight per 1000ft – XLP: | 242.6 Lbs |
Weight per 1000ft – Poly: | 234.2 Lbs |
Rating – XLP: | 160 Amps |
Rating – Poly: | 160 Amps |
Applications: To supply 120 volt aerial service for temporary service at construction sites, outdoor or street lighting. For service at 600 volts or lower at a conductor temperature of 75°C maximum.
Construction: Concentric strand or compressed 1350-H19 conductor, polyethylene or crosslinked polyethylene insulation, concentric strand AAC, ACSR, or 6201 alloy neutral messenger.
Standards:
- B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
- B-231 Aluminum Conductors, Concentric-Lay-Stranded.
- B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
- B-399 Concentric-Lay_Stranded 6201-T81 Aluminum Alloy Conductors.
- B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
- Duplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.