Conductors: Class B compressed unilay or compressed round aluminum alloy 1350 per ASTM.
Phase Insulation: Extruded composite three-part cable insulation consisting of an inner layer of low density polyethylene, encapsulated channels of self-healing EPDM-based Prysmian SR compound and an outer layer of black, sunlight resistant, high-density polyethylene.
Neutral Insulation: Extruded composite three-part cable insulation consisting of an inner layer of low density polyethylene, encapsulated channels of self-healing EPDM-based Prysmian SR compound and an outer layer of black, sunlight resistant, high-density polyethylene with extruded yellow stripes for neutral identification.
Assembly: For multiple cable assemblies, one, two, or three phase conductors with one neutral twisted together.
Cable Markings: Sequential footage markings on one phase conductor. Phase identification surface printed in white ink: 1/C – “Phase A”, 1/C – “Phase B”, 1/C – “Phase C”, as applicable.
Applications: Secondary UD Power Cable, with aluminum conductors and a cross-linked polyethylene insulation that is formulated for a balance of flexibility and mechanical toughness. Superseal® uses a patented self-healing technology that repairs damage to the insulation there by reducing secondary cable failures.
Options:
• Series 8000 Aluminum Conductor(s)
• Paralleled
• Solid Black Neutral
Installation:
• Direct Buried
• Underground Duct
• Wet Locations
• Dry Locations
• Utility Secondary
Specifications and ratings:
• ICEA- ICEA S-81-570 (as applicable)
• RUS- RUS Accepted
• For 90°C Wet or Dry Operation.
technical specifications: | |
phase conductor | 1/0 awg al |
code name | Harvard |
phase insulation thickness (mils) | 80 |
phase conductor diameter (in) – (a) | 0.352 |
outside diameter (in) – (b) | 0.52 |
cable weight (lbs/kft) | 150 |
minimum bending radius (in) | 3 |
† ampacity (amps) – 90°c in duct | 135 |
† ampacity (amps) – 90°c direct buried | 200 |
prysmian cable part number | Q0Q320A |