Product Details
Outer Jacket:
• Material: PVC – Polyvinyl Chloride
• Nom. Wall Thickness (mm): 2.1336
• Outer Jacket Ripcord: Yes
Mechanical Charactertistics (Overall):
• UL Temperature Rating: 75°C Wet, +90°C Dry
• Bulk Cable Weight: 678.619 Kg/Km
• Max. Recommended Pulling Tension: 1846.003 N
• Min. Bend Radius/Minor Axis: 228.600 mm
Electrical Characteristics (Overall):
• Nominal Outer Shield DC Resistance @ 20°C (Ohm/km): 16.635
• Max. Recommended Current: 2.6 Amps/conductor @ 30C
Flame Test:
• UL Flame Test: UL1685 Vertical Tray Flame Test
• CSA Flame Test: FT4
technical specification: | |
awg | 18 |
# paris | 16 |
stranding | 7×26 |
no. of conductors | 32 |
conductor material | bare copper |
outer shield – type | tape |
outer shield – material | aluminum foil-polyester tape |
overall cable- nominal dia. (mm) | 22.809 |
belden cable part number | 1052A |