Description:
• 16 AWG pairs stranded (7×24) tinned copper conductors, PVC insulation, individual Beldfoil® plus a polyester isolation tape, overall Beldfoil shield (100% coverage), PVC jacket.
Insulation:
• Material: PVC – Polyvinyl Chloride
Outer Shield Drain Wire AWG:
• AWG: 18
• Stranding: 7×26
• Material: TC – Tinned Copper
Outer Jacket:
• Material: PVC – Polyvinyl Chloride
• Nom. Wall Thickness (mm): 1.143
• Outer Jacket Ripcord: Yes
Mechanical Charactertistics (Overall):
• Installation Temperature Range: -25°C To +90°C
• Operating Temperature Range: -40°C To (+105°C Dry, +75°C Wet)
• Non-UL Temperature Rating: 105°C
• Bulk Cable Weight: 181.560 Kg/Km
• Min. Bend Radius/Minor Axis: 81.280 mm
Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• CEC/C(UL) Specification: CIC
• CSA Specification: C22.2#239, Type CIC, C22.2 #0.3 Clause 4.31 Low Acid Test
• EU Directive 2011/65/EU (ROHS II): Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 01/01/2006
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes
Electrical Characteristics (Overall):
• Nom. Conductor DC Resistance @ 20°C (Ohm/km): 12.1397
• Nominal Outer Shield DC Resistance @ 20°C (Ohm/km): 16.7331
• Max. Operating Voltage – Other: 300 (CEC CIC)
Flame Test:
• C(UL) Flame Test: FT4
Suitability:
• Suitability – Indoor: Yes
• Suitability – Outdoor: Yes
Plenum/Non-Plenum:
• Plenum (Y/N): No
technical specification: | |
awg | 16 |
# pairs | 1 |
stranding | 7×24 |
no. of conductors | 2 |
conductor material | tinned copper |
outer shield – type | tape |
outer shield – material | aluminum foil-polyester tape |
overall cable- nominal dia. (mm) | 8.128 |
belden cable part number | 22646 |