Technical Data
• Special PVC control cables adapted
to DIN VDE 0276 part 627,
DIN VDE 0285-525-2-51 /
DIN EN 50525-2-51,
with insulation thickness for 1 kV
and to UL Std.758 Style 21179
Temperature Range
• Flexing -5°C to +80°C
• Fixed installation -40°C to +80°C
Nominal Voltage
• VDE U0/U 600/1000 V
• UL/CSA 1000 V
Test Voltage
• 4000 V
Breakdown Voltage
• Min.8000 V
Insulation Resistance
• Min. 20 MOhm x km
Minimum Bending Radius
• Flexing 10x cable Ø
• Fixed installation 5x cable Ø
Radiation Resistance
• Up to 80×106 cJ/kg (up to 80 Mrad)
Coupling Resistance
• Max 250 Ohm/km
Cable Structure
• Bare copper fine wire conductors acc. to DIN VDE 0295 cl.5 BS 6360
cl.5 and;IEC 60228 cl.5
• Core insulation of special PVC compound type TI2 to
DIN VDE 0207-363-3 / DIN EN 50363-3
and class 43 acc to UL Std 1581
• Core identification to DIN VDE 0293
black cores with continuous white
numbering
• GN-YE conductor 3 cores and above
in the outer layer
• Cores stranded in layers with
optimal lay length
• PVC-insulated inner sheath TM2 to
DIN VDE 0207-363-4-1/DIN EN 50363-4-1,
class;43 acc to UL Std.1581
• Braided screen of tinned Cu wires,coverage approx 85%
• Outer sheath of special PVC
compound type TM2 to
DIN VDE 0207-363-4-1/DIN EN 50363-4-1
and class 43 acc to UL Std.1581
• Sheath colour: black (RAL9005) or
grey (RAL7001)
• With meter marking
Properties
• Extensively oil resistant,
oil-/chemical resistance
see “Technical;Informations”
• UV resistant (building with black sheath)
• The materials used during manufacturing
are cadmium-free contain no silicone
and are free from substances harmful
to the wetting properties of lacquers
Tests
• PVC self-extinguishing and flame retardant
acc to DIN VDE 0482-332-1-2,
DIN;EN 60332-1-2 IEC 60332-1-2
(equivalent DIN VDE 0472 part 804
test method B) UL VW-1 CSA FT1
Note
• G = with GN-YE conductor x = without GN-YE conductor (OZ)
• AWG sizes are approximate equivalent
values The actual cross section is in mm².
• Unscreened analogue type: JZ-600 UL/CSA
Application
PVC control cable for measuring,monitoring and control purposes in tool machinery, conveyor belts and production lines in machinery, in air
conditioning, in foundries and steel mills. Suitable for installation for flexible use for medium mechanical stresses with free movement without tensile
stress or forced movements in dry, moist and wet rooms as well as outside (fixed installation, building with black sheath) Is not suitable to be used
as direct burrial- or as underwater cable. Interference-free;transmission of signals and pulses is assured by the high degree of screening.
Technical Specification | |
AWG | 10 |
No.Cores x cross-sec. mm² |
5 G 6 |
Outer ø app.mm |
20,7 |
Cop. weight kg/km |
442,0 |
Weight app. kg/km |
1105,0 |
Helukabel Part Number | 12457 |