Technical Data:
• Special PVC command cable, approved to UL Style 2464, cores for AWG 26-20 to UL Style 1061/1729 for AWG 18-16 to UL Style 1007/1569
Temperature Range:
• flexing -10°C to +80°C
• fixed installation -20°C to +80°C
Nominal Voltage: 300 V Tests
Test Voltage: 1500 V
Breakdown Voltage: min. 3000 V
Minimum Bending Radius:
• flexing 15x cable Ø
• fixed installation 7,5x cable Ø
Cable Structure:
• Tinned copper conductor, fine wire, AWG 26-20 to ASTM-B 174-95 class J-M, AWG 18-16 to ASTM-B 286 Conductor make-up to: 0,14 mm² = 7×0,162 mm, 0,23 mm² = 7×0,202 mm, 0,34 mm² = 7×0,254 mm, 0,56 mm² = 7×0,32 mm, 0,82 mm² = 19×0,235 mm, 1,30 mm² = 19×0,31 mm
• Core insulation of special PVC class 43 respectively semirigid acc. to UL Std.1581 tab.50.182 and 50.183
• Core identification to DIN 47100 or international colour code
• Cores stranded in layers with optimal lay length
• Outer sheath of special PVC class 43 acc. to UL Std.1581 tab.50.182
• Sheath colour: black (international colour code) grey (DIN 47100 – preferred type)
Properties:
• The materials used during manufacturing are cadmium-free, contain no silicone and are free from substances harmful to the wetting properties of lacquers
• To a large extent resistant to Oil, Solvents, Acids, Lyes
Tests: PVC flame retardant acc. to UL VW-1, CSA FT1
Note:
• AWG sizes are approximate equivalent values. The actual cross section is in mm².
• Screened analogue type: command cable UL (LiYCY)
Application:
• As a flexible connector and connecting cable, as control, signal and measuring line of machine tools, conveyor belts and plant construction, air conditioning systems, in foundries and steel mills.
• = Product conforms with Low-Voltage Directive 2014/35/EU.
technical specification: | |
awg-no. | 26 |
no.cores x cross-sec. mm² | 10 X 0,14 |
sheath colour | black |
outer ø app. – mm | 5,6 |
cop. weight – kg/km | 13,4 |
weight app. – kg/km | 38,0 |
helukabel part number | 83049 |