Technical Specifications: | |
Catalog Number | HW277 01608 |
Size AWG | 16 |
Number of Conductors | 8 |
Nominal Diameter (inches) |
0.581 |
Weight (lbs/Mft.) |
265 |
Ampacity 110° C | 12 |
Ampacity 100° C | 11 |
Ampacity 95° C | 11 |
Specifications:
- HW277
- MULTI-CONDUCTOR
- CONTROL CABLE
- 0.6/1kV Armored 110°C
- Gexol® Insulation
- Made in the USA
Application:
Designed and constructed for the demanding environments of
offshore drilling and petroleum facilities located throughout the world.
Conductors:
Soft annealed flexible stranded tinned copper per IEEE 1580 Table 11.
Insulation:
Flame Retardant Cross-linked Polyolefin, meeting the requirements
for Type P of IEEE 1580 and Type X110 of UL 1309/CSA C22.2 No.
245. Color Code: IEEE1580 Table 22. Sizes 1/0 and Larger: Black with
Phase ID Imprint.
Jacket:
Black, arctic grade, flame retardant, oil, abrasion, chemical and
sunlight resistant thermosetting compound meeting UL 1309/CSA
C22.2 No. 245 and IEEE 1580.
Armor:
Basket weave wire armor per IEEE 1580 and UL 1309/CSA C22.2
No. 245. Bronze standard. Tinned copper available by request.
Ratings & Approvals :
- American Bureau of Shipping (ABS)
- Transport Canada
- Det Norske Veritas (DNV)
- Lloyd’s Register of Shipping (LRS)
- NVE 95/1696, FAL
- UL listed as Marine Shipboard Cable
- United States Coast Guard
- CSA listed as Marine Shipboard Cable
Features:
- High strand count conductors make this product extremely flexible, easier to install and more resistant to vibration than Type MC, IEC spec or commercial cables.
- Lower dielectric constant and higher insulation resistance reduces electrical losses.
- Excellent resistance to moisture produces stable electrical properties throughout the life of the cable.
- In fire conditions, non chlorinated flame retardant system produces less toxic and less corrosive gasses.
- Dual certified IEEE 1580 Type P and UL 1309/CSA C22.2 No. 245 Type X110.
- Highest ampacity ratings: ABS 100°C, DNV 95°C, LRS 95°C, Transport Canada 95°C
- Severe cold durability: exceeds CSA cold bend/cold impact (-40/-35° C)
- Flame retardant: IEC 60332-3 Category A and IEEE 1202