Interlocked Armor Power Cable – 4 Gauge – 3 Conductor
Technical Specifications: | |
Size (AWG or kcmil): | 4 |
No. of Conductors | 3 |
Net Weight: | 1115 |
Overall Diameter (Inches): | 1.40 |
Insulation Thickness (Mils): | 115 |
Jacket Thickness (Mils): | 50 |
No. of Strands: | 7 |
Class 1 Div.2 Connector No.: | 424CU06 |
Rain Tight Connector No.: | 416MC06 |
Specifications:
- Interlocked Armor – Power Cable
- 5KV UL Type MV-105 or MC, CT Use, 105°C
- Non-Shielded, EPR Insulation
- 133% Insulation Level
- Aluminum Armor
- Copper Conductor
Application:
For use in harsh environments where maximum conductor protection is required. Used for primary power and feeder circuits in a broad range of commercial and industrial power distribution systems. Approved for use in wet or dry locations at 105°C, for installation indoors or outdoors, aerially, in conduits, ducts, cable trays or direct burial in circuits not exceeding 5,000 volts. May be used in NEC Class I and II, Division 2 and Class III, Division 1 and 2 hazardous locations. National Electric Code approved for use at 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions. Aluminum interlocked armor cable is recommended as an economical alternative to wire in conduit systems.
Conductors:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact), with a semi-conducting conductor shield.
Insulation:
Ethylene propylene rubber (EPR) per ICEA S-96-659.
Grounding Conductor:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 sized in accordance with UL Standard 1072.
Armor:
Aluminum interlocked tape armor per UL Standard 1072 and applicable ICEA standards. Also available in galvanized steel armor.
Jacket:
Yellow sunlight-resistant PVC per UL Standard 1072 and applicable ICEA standards.
Flame Tests:
- UL and IEEE 383 70,000 BTU/hr flame test
- IEEE 1202 (2AWG and larger) CSA FT4 flame test
- ICEA 210,000 BTU/hr flame test
Color Code:
ICEA Method 4
Additional Standards:
NEMA WC71
Connectors:
- Explosion Proof, Class 1 Division 2: 424CU series – exterior components – aluminum, interior components – nickel-plated brass
- Rain Tight: 416MC series – all nickel-plated brass
- See 424MA series in Section J.