Description:
Hunter 2/0-2/0-2/0 Triplex cable is good for underground secondary distribution circuits not exceeding 600 Volt. Its three conductors have the same gauge sizes of 2/0 AWG; two phase conductors and a neutral wire. The cable can be directly buried underground (maximum 245 amps) or used in raceways and ducts (maximum output of 180 amps). The cable conducts a maximum of 600 volts and functions well in temperatures below 90°C.
Applications:
#2/0 Hunter Aluminum Underground Distribution Cable specifically designed for underground distribution systems. In extreme environmental conditions, the cross-linked polyethylene is used since it can withstand temperatures of up to 90°C.
Conductors:
They are made of aluminum alloy which are compressed in 1350-H19. Only 99.5% of the conductor is made of aluminum the rest is made of zinc, copper and silicon.
Insulation:
The insulation is made of standard polyethylene or cross-linked polyethylene.
Features:
• Can resist high temperatures of up to 90°C
• Corrosion resistant conductors
• Heat and moisture resistant insulation
• Lead free triplex wire
• 600 volt URD cable
Standards:
• ASTM B-901
• ICEA S-105-692
• Federal Specification J-C-30B
• RUS Accepted
Technical Specifications: | |
Phase Conductor Size AWG: | 2/0 |
Phase Conductor Stranding: | 11 |
Phase Conductor Insulation Thickness: | 80 mls |
Base Neutral Messenger Size AWG: | 2/0 |
Base Neutral Strand: | 11 |
Diameter Single Phase Conductor (Mils): | 555 |
Diameter Complete Cable (O.D.) (Mils): | 1199 |
Weight Per 1000ft Total (Lbs.): | 535 |
Allowable Ampacity 90C (Amps): | 245 |
Allowable Ampacity in Ducts (Amps): | 180 |