Sizes 3-23: Stranded uncoated copper conductor, extruded silicone rubber insulation, glass braid, braid covering. Standard Identification Code by Method 1. Three conductors cabled with fillers, binder or combination binder/barrier.
LSTSGU: cross-linked polyolefin, surface marking.
LSTSGA: cross-linked polyolefin jacket braided aluminum armor, paint. Sizes 50-400: Same, except silicone rubber-glass tape insulation, no glass braid or braid covering. Letter Identification Code by Method 5, binder only between cabled assembly and jacket.
LSTSGS: Same as LSTSGU except double overall shield.
technical specifications: | |
conductor size : awg or mcm | 3/0 |
number of conductors in cable | 3 |
cable type designation | lstsgu-150 |
area of each conductor (mcm) | 167.800 |
cable** overall diameter max. (inch) | 1.515 |
cable weight per ft. appox. (lbs) | 2.465 |
radius of bend min. (inch) | 9.5 |
cdr id | std-1 |
rated voltage max (rms) | 1000 |
ampacity, each conductor (amps,max) – dc or 60 hz – 40°c ambient | 235 |
ampacity, each conductor (amps,max) – dc or 60 hz – 50°c ambient | 216 |
ampacity, each conductor (amps,max) – 400 hz – 40°c ambient | 224 |
ampacity, each conductor (amps,max) – 400 hz – 50°c ambient | 206 |
nsn | 6145-01-201-9505 |
seacoast military part number | mil-c-24643/16-09un |